CO-Sensor (A1)  
Measurement range 0...1.000 ppm
Accuracy ±5 ppm + max. ±5% f. mv (at 20°C, 50% r.H.)
Temperature dependency ±5 ppm / K
Response time (t90) < 5 min
Long term stability ±1% FS/year
Sensor Electrochemical gas sensor
CO2-Sensor (A2, A22, A23)  
Measurement range A2 0...10.000 ppm
Measurement range A22 0...20.000 ppm
Measurement range A23 0...50.000 ppm
Accuracy ±50 ppm + 2% v. MW at 0-2000 ppm, ±50 ppm + 3% v. MV at 0-5000 ppm, else ±100 ppm + 5% v. MV (at 20°C, 1013 mbar, auto calibration ON)
Temperature dependency ±5 ppm / K
Druckabhängigkeit compensated if option "air pressure sensor" is selected, else 1.6% of the meassurement value / kp difference to 1013mbar
Response time (t90) < 1 min
Long term stability ±1% FS/year
Sensor Nondispersive infrared sensor (NDIR)
Automatic calibration The automatic drift compensation takes place in the interval of 7 days. This ensures an excellent long-term stability. The device must be supplied with fresh air within this interval (during continuous operation) for at least 10 minutes. This function can
Manual calibration Manual adjustment to 400 ppm can be executed via registry-command.
Oxygen sensor (A31, A32)  
Measurement range oxygen A31 0…25% vol.
Measurement range oxygen A32 0…100% vol.
Accuracy ±5 µg/m³ + max. ±4% FS (@ 20°C, 45% r.H., 1013 mbar)
Temperature dependency ±1% FS / 10 K
Long term stability ±0,2% FS/year at auto calibration ON
Response time (t90) <1s
Air quality sensor for mixed gas -VOC (A4)  
Measurement range VOC 0-100% (good / bad air quality, referring to the calibration gas)
Accuracy ± 10% FS (at 20°C, 50% r.H. and auto-calibration ON)
Temperature dependency ±0,2% FS/K
Response time (t90) < 1 min
Long term stability ±5% FS/year (auto-calibration ON)
Sensor metal oxide VOC-sensor
Automatic calibration The automatic drift compensation takes place in the interval of 7 days. This ensures an excellent long-term stability. The device must be supplied with fresh air within this interval (during continuous operation) for at least 10 minutes. This function can
Manual calibration Manual zeropoint can be setted via registry-command to 10%
Sensitivity Sensitivity can be varied at three levels via registry-command to 10%
Particulate Matter Sensor PM2.5/PM10 (A51)  
Measurement range particulate matter 0 μg/m³ ... 1000 μg/m³
Accuracy ±5 µg/m³ + max. ±4% FS (@ 20°C, 45% r.H., 1013 mbar)
Temperature dependency ±1% FS / 10 K
Long term stability ±1% FS/year
Response time (t90) <1s
Flow transducer (F11 or F12 - with pendulum sensor, mounting flange within scope of delivery)  
Measuring principle calorimetric measuring method
Measurement range flow F11 0...5 m/s
Measurement range flow F12 0...20 m/s
Calculation air flow F11 0-50.000 m³/h, formula and parameters via registry
Calculation air flow F12 0-200.000 m³/h, formula and parameters via registry
Accuracy ±0,3 m/s + max. ±4% FS (@ 20°C, 45% r.H., 1013 mbar)
Temperature dependency ±1% FS/ 10 K
Long term stability ±1% FS/year
Response time (t90) <1s
operating range F11 0,3...5 m/s
operating range F12 0,3...20 m/s
Humidity / temperature transducer (H1T1 or H2T1 - heated temporarily or permanently)  
Measurement range r.H. 0-100% r.H.
Accuracy humidity ±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C)
Measurement range temperature -20°C...50°C
Accuracy temperature ±0,5 K
Calculated thermodynamic values dew point temperature, abs. humidity, air fuel ratio, enthalpy, wet bulb temperature, vapour pressure
Long term stability ±1% FS/year
Sensors Combined humidity and temperature sensor
Sensor protection high-humidity range H1T1 condensation protection by heating function at more than 95% r.H. ( holding function of the meassured values during heating function).
Sensor protection high-humidity range H2T1 Kondensationsschutz durch Dauerheizung ca. 3 K über Umgebungstemperatur
Flow rate < 2 m/s
Motion Sensor (M1)  
Measurement range motion motion yes/no, apex angle 90°/110° on 360° range, reach 10 m
Response time (t90) < 1 s
Sensor infrared motion sensor MTS 10/360, photodiode
Pressure Sensor (P2 oder P22 oder P23)  
Measurement range pressure P2 -100...+100 Pa
Measurement range pressure P22 -500...+500 Pa
Measurement range pressure P23 -5000...+5000 Pa
Calculation air flow P2 0...4.000 m³/h of the differential pressure uo to 100Pa, formula and parameters via registry
Calculation air flow P22 0...20.000 m³/h of the differential pressure uo to 500Pa, formula and parameters via registry
Calculation air flow P23 0...200.000 m³/hof the differential pressure uo to 5000Pa, formula and parameters via registry
Accuracy Difference pressure
Temperature dependency Difference pressure
Linearity inaccuracy Difference pressure / Air Pressure
Offset can be set at the registry
Output attentuation can be set at the registry
Pressure resistance 5-times of measurement range
Manual zero-point adjustment Manual zero-point adjustment can be executed
Air Pressure Sensor (P4)  
Measurement range atmospheric / barometric pressure 500-1150 mbar
Accuracy ±3 mbar (at 20°C)
Temperature dependency 1 mbar / 10 K
Linearity inaccuracy ±1% FS
Offset can be set at the registry
Output attentuation can be set at the registry
   
General  
Supply voltage 24V DC +/-5%
Current consumption typically 100 mA, (depending on MODBUS parameters and selected backlight) plus around 20ma/sensor
Digital output Modbus RTU
Electrical connection push-in terminal, no tools required, time-saving
Display programmable display at 3 levels, customer-specific interfaces optional
Housing Polycarbonate PC UL 94 V0 with hinge locks, color light grey
Cable gland Cable connection 12mm with stain relief
Dimensions Housing
Alarm transmitter (piezo) freely programmable, volume approx. 85db at a distance of 10cm
Protection type Housing/electroic IP65 (IP20 at option particulate matter and/or CO2)
Protection type sensor attachments IP30
Protection class III
Sensor protection (1) r. / Temp, VOC, CO2
Working- and Storage temperature -20...+50°C
Range of application Ambient air monitoring, pollution-free, non-condensing air up to max. 98% r.H. (except harmful gases in accordance with sensor specifications)
Attachments at the device V2A tubes and/or V2A sinter filter
Option clamping connectors / screw connectors Steel M12 industrial standard
special features When calculating different sizes, depending on the selected sensor configuration, air pressure, air density, etc. are included. If these values are not available internally from sensors, they can be entered by the Modbus master into the corresponding regi