Lambda Transmitter LT3 LS2, Đại lý Lamtec tại Việt Nam
Đại lý Lamtec tại Việt Nam
O2 measuring
Measuring directly inside flue gas
Applicable up to 1200 °C
Also available in Ex-version
Measuring range : | O2: 0 - 21 % (configurable) |
Housing: | Sheet steel |
Protection type following DIN 40050 | IP66, without display IP54 |
Dimensions (HxBxT) mm | 300 x 300 x 120 |
Color | Grey, RAL 7035 |
Weight | Appr. 6kg |
Ambient temperature operation: |
-5 °C ... + 60 °C |
Ambient temperature transport and storage: |
-20 °C ... + 70 °C |
Power supply: | 120 VAC / -30%...230 VAC / +10%, 50...60Hz |
Power consumption: | 30W (normal operation) 69W (heating) |
Resolution O2: |
0,1 Vol. % O2 |
Preciseness of measuring: (with combination probe KS1D) |
O2: ±5% of measurement value (max ± 0,3 Vol. % O2) |
Setting time (60 % time): | O2: T 60 < 3 s (unfiltered) |
Time for readiness with probe LS2 (cold start-up) |
Appr. 10min after „POWER ON“ (Initial start-up appr. 60min) |
Analogue output, via analogue output module: | Analogue output 1 (O2 measurement value) - Range of setting: 0…25 % O2 - Factory setting 0…10 Vol.% O2 -> 4…20 mA |
Digital outputs via digital output module: |
Optional |
Control element: | Integrated LT3 User Interface with LCD-graphic display 45x27 mm (BxH) External start-up assistant with LCD-graphic display 60x32 mm (BxH) (Option) |
Interface: | LAMTEC System Bus (LSB) |