GFI70 300, GFI70 300 Lamtec, Đại lý Lamtec tại Việt Nam
Đại lý Lamtec tại Việt Nam
Fuel: natural gas, LPG (liquid propane gas), coke gas, refinery gas
Thermal power up to 3MW in special design up to 6MW
Flame length up to 3m
Intermittent- or continuous operation
SIL 3 certified
Protection class IP 65
Available for hazardous Areas
Supply voltage: | 220 - 230 VAC (-15/+10 %). 50/60 Hz 120 – 127 VAC (-15/+10 %). 50/60 Hz |
Ignition voltage: | 8 kV |
Power consumption: | 100 VA ignition transformer ≤10 KV flame scanner |
Electrical connection: | Plug with mating caonnector (standard) Plug with mating connector with pre-assembled cable Cable permanently connected |
Cable length: | 2 m – 100 m, Standard = 5 m |
IP protection: | IP 65/IP 67 |
Housing: | Sea water resistant aluminium (standard) stainless steel (1.4301/1.4571) |
Coating: | Non (standard) C2/C4 painting (option) |
Tube length: |
240 – 6.000 mm |
Tube: | Stainless steel 1.4301, heat resistant end tube1.4841 (standard) Stainless steel 1.4571 heat resistant end tube 1.4841 (option) |
Fuel gas: | Natural gas, propane/butane (standard) coke oven gas, refinery gas (option) |
Fuel gas supply pressure: | 50 – 200 mbar above combustion pressure (standard) Orifice for higher pressure (option) |
Air suppl pressurer: | Depending on the size |
Cooling air flow: | Depending on the size, at least 50 % of combustion air flow |
Approvals:
|
For SIL 3 flame monitoring device F130I: |